IEC 62351-6-2020 pdf free download – Power systems management and associated information exchange – Data and communication security – Part 6: Security for IEC 61850

02-14-2022 comment

IEC 62351-6-2020 pdf free download – Power systems management and associated information exchange – Data and communication security – Part 6: Security for IEC 61850.
1.3Code Component distribution
There is currently no code component scheduled for the code component downloading area.
2Normative references
The following documents are referred to in the text in such a way that some or all of their contentconstitutes requirements of this document. For dated references, only the edition cited applies.
For undated’references,the latest edition of the referenced document(including anyamendments) applies.
IEC 61850-6, Communication networks and systems for power utility automation – Part 6:Configuration description language for communication in electrical substations related to IEDs
IEC 61850-7-3,Communication networks and systems for power utility automation – Part 7-3:Basic communication structure -Common data classes
IEC 61850-8-1,Communication networks and systems for power utilityautomation -Part 8-1: Specific communication service mapping (ScSM) – Mappings to MMs (ISO 9506-1and lso 9506-2) and to isOnIEC 8802-3
IEC 61850-8-2, Communication networks and systems for power utility automation – Part 8-2:Specific communication service mapping (scSM)- Mapping to Extensible Messaging PresenceProtocol(XMPP)
IEC 61850-9-2,Communication networks and systems for power utility automation – Part 9-2;Specific communication service mapping (scSM) – Sampled values over ISO/IEC 8802-3
IEC TS 62351-1,Power systems management and associated information exchange – Dataand communications security – Part1: Communication network and system security -lntroduction to security issues
IEC TS 62351-2,Power systems management and associated information exchange – Dataand communications security – Part 2: Glossary of terms
IEC 62351-4:2020,Power systems management and associated information exchange -Dataand communications security- Part 4:Profiles including MMS and derivatives
IEC 62351-9,Power systems management and associated information exchange – Data andcommunications security- Part 9: Cyber security key management for power system equipment
ISO/IEC 13239,Information technology – Telecommunications and information exchangebetween systems – High-level data link control(HDLC) procedures
ISOIEC 9594-8 | Rec.ITU-T X.509: Information technology – Open Systems Interconnection -The Directory: Public-key and attribute certificate frameworks
RFC 2104,HMAC: Keyed-Hashing for Message Authentication
RFC 5905,Network Time Protocol Version 4: Protocol and Algorithms Specification
RFC 8052,Group Domain of Interpretation(GDOI) Protocol Support for IEC 62351 SecurityServices
NIST Special Publication 800-38D, Recommendation for Block Cipher Modes of OperationGalois/Counter Mode (GCM and GMAC)
3 Terms,definitions and abbreviated terms3.1Terms and definitions
For the purposes of this document,the terms and definitions given in IEC TS 62351-2 andIEC61850-2 apply.
Iso and IEC maintain terminological databases for use in standardization at the followingaddresses:
IEC Electropedia: available at http://www.electropedia.orgl
Iso Online browsing platform: available at http://www.iso.orglobp
3.1.1
electronic security perimeter
logical border surrounding a network interconnecting critical cyber assets
3.1.2
client
functional unit that establishes an association and issues requests and receives services froma server.
3.1.3server
functional unit that receives an association from a Client and provides services requested bythe Client
4 Security issues addressed by this document 4.1 Operational issues affecting choice of security options For applications using Layer 2 IEC 61850-8-1 GOOSE and Layer 2 IEC 61850-9-2 Sampled Value and requiring 3 ms response times, multicast configurations and low CPU overhead, encryption is not recommended. Instead, the communication path selection process (e.g. the fact that Layer 2 GOOSE and SV are supposed to be restricted to a logical substation LAN) shall be used to provide confidentiality for information exchanges. However, this document does define a mechanism for allowing confidentiality for applications where the 3 ms delivery criterion is not a concern.IEC 62351-6 pdf download.

Download infomation Go to download
Note: If you can share this website on your Facebook,Twitter or others,I will share more.
IEC 61300-2-40-2000 pdf free download – Fibre optic interconnecting devices and passive components – Basic test and measurement procedures – Part 2-40: Tests – Screen testing of attenuation of single- mode tuned angled optical connectors IEC Standards

IEC 61300-2-40-2000 pdf free download – Fibre optic interconnecting devices and passive components – Basic test and measurement procedures – Part 2-40: Tests – Screen testing of attenuation of single- mode tuned angled optical connectors

IEC 61300-2-40-2000 pdf free download - Fibre optic interconnecting devices and passive components – Basic test and measurement procedures – Part 2-40: Tests – Screen testing of attenuation of single- mode tuned angled optical connectors. 1.1Scope and...
Download Now

LEAVE A REPLY

Anonymous netizen Fill in information