BS EN 1264-5-2021 pdf free download

03-01-2022 comment

BS EN 1264-5-2021 pdf free download.Water based surface embedded heating and cooling systems Part 5: Determination of the thermal output for wall and ceiling heating and for floor, wall and ceiling cooling
The EN 1264 series gives guidelines for surface embedded heating and cooling systems installed in buildings, residential and non-residential (e.g. office, public, commercial and industrial buildings) and focuses on systems installed for the purpose of thermal comfort. The EN 1264 series gives guidelines for water based heating and cooling systems embedded into the enclosure surfaces of the room to be heated or to be cooled. It also specifies the use of other heating media instead of water, as appropriate.
The EN 1264 series specifies standardized product characteristics by calculation and testing the thermal output of heating for technical specifications and certification. For the design, construction and operation of these systems, see EN 1264-3 and EN 1264-4 for the types A, B, C, D, H, I and J. For the types E, F and G, see the EN ISO 11855 series.
The systems specified in the EN 1264 series are adjoined to the structural base of the enclosure surfaces of the building, mounted directly or with fixing supports. The EN 1264 series does not specify ceiling systems mounted in a suspended ceiling with a designed open air gap between the system and the building structure which allows the thermally induced circulation of the air. The thermal output of these systems can be determined according to the EN 14037 series and EN 14240. EN 1264-5 specifies the recalculation of values determined in EN 1264-2 for the system in question. It enables the conversion of the calculation and measurement results of EN 1264-2 into results for other surface orientations in the room, i.e. for ceiling and wall heating, as well as for the application as cooling surfaces, i.e. for floor, ceiling and wall cooling. The test results of EN 1264-2 are the basis of all calculation, whether or not the system in question is used for heating or cooling application.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1264-1, Water based surface embedded heating and cooling systems
— Part 1: Definitions and symbols EN 1264-2:2021, Water based surface embedded heating and cooling systems
— Part 2: Floor heating: Methods for the determination of the thermal output using calculations and experimental tests
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1264-1 apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/
4 Calculation method
The calculation method is based on the results obtained in EN 1264-2:2021. The method enables the conversion of these results into results for other surfaces in the room (ceiling and wall heating). The method is also applicable for all cooling surfaces (floor, ceiling, wall cooling). The change in the surface thermal resistance ΔR α = Δ(1/α) influences the temperature field within the system in the same way as a change in the thermal resistance of the surface covering ΔR λ,B . This is based on the assumptions that all other boundary conditions are unchanged and that in case of cooling the dew point is not reached. This leads to the Formula (1).
The gradient of the characteristic curve K H (Formula (2)) is also referred to as equivalent heat transmission coefficient. The characteristic curve gives the relationship between the specific thermal output q and the temperature difference Δϑ between the heating medium and the room (heating system) or between the room and the cooling medium (cooling system):
https://down.qitubk.comis the gradient of the characteristic curve, see Formula (2), of the heating/cooling system which shall be calculated, with the actual thermal resistance of the covering R λ,B ≥ 0 and the respective value ∆R α (see Table A.1);BS EN 1264-5 pdf download.

Download infomation Go to download
Note: If you can share this website on your Facebook,Twitter or others,I will share more.
BS ISO 9349-2017 pdf free download BS Standards

BS ISO 9349-2017 pdf free download

BS ISO 9349-2017 pdf free download.Ductile iron pipes, fittings, accessories and their joints — Thermal preinsulated products 4 Technical requirements 4.1 General A preinsulated pipe (or fitting) is generally manufactured by injection moulding the polyurethane foam thermal...
Download Now
BS EN 2033-2017 pdf free download BS Standards

BS EN 2033-2017 pdf free download

BS EN 2033-2017 pdf free download.Aerospace series — Strips, cold rolled in steel, Thickness 0,1 mm ≤ a ≤ 2,5 mm — Dimensions This European Standard specifies the dimensions and tolerances of: Strips, cold rolled in steel...
Download Now
BS EN 2017-1989 pdf free download BS Standards

BS EN 2017-1989 pdf free download

BS EN 2017-1989 pdf free download.Specification for Bearings-airframe rolling double row self aligning ball bearings in corrosion resisting steel diameter series 2 — Dimensions and loads This standard specifies the characteristics, of double row self aligning ball...
Download Now

LEAVE A REPLY

Anonymous netizen Fill in information